6
4.1 Explanation of UPS Mode Control Logic
ON
28.5V
26.5V
28.5V
28.5V
ON
OFF
ONON
By pass
mode
Inverter
Mode
Battery
voltage
ON
OFF
Solar charger
state
AC charger
state
ON
OFF
ON
OFF
OFF
26.5V
28.5V
OFF
ON
29.0V
ON
OFF
OFF
ON
Power-On Re-power-on
21V(Shut-down)
t
t
t
t
t
Utility
Power
ON
OFF
22.5V
(Alarm)
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
25.4V
t1 t2 t3 t4 t5 t6 t8 t9 t10 t11 t12t7
26.5V
Figure 4.1: Diagram of UPS Mode Control Logic
t1: To ensure the battery is at full capacity, when the TN-1500 is turned on, the
t2: When the batteries are full (battery voltage around 28.5V), both the AC and
CPU will execute the "Bypass Mode" automatically connecting the AC main to
the load. In the meantime, it will activate both the AC charger and solar
solar charger will be turned off by the CPU to prevent overcharging and
reducing the battery lifetime. In the meantime, the system will remain in the
"Bypass Mode" and AC electricity provided to the loads is coming from public
utility.
charger to simultaneously charge the batteries.